IEC Voltage Standards and Recommendations
Three-phase four-wire or three-wire systems
| Single-phase three-wire systems |
Nominal voltage (V)
| Nominal voltage (V) |
| 50 Hz | 60 Hz | 60 Hz
|
-
| 120/208 | 120/240 |
| - | 240 | - |
230/400(1)
| 277/480
| - |
| 400/690(1) | 480 | - |
| - | 347/600 | - |
| 1000 | 600 | - |
(1)
The nominal voltage of existing 220/380 V and 240/415 V systems shall
evolve toward the recommended value of 230/400 V. The transition period
should be as short as possible and should not exceed the year 2003.
During this period, as a first step, the electricity supply authorities
of countries having 220/380 V systems should bring the voltage within
the range 230/400 V +6 %, -10 % and those of countries having 240/415 V
systems should bring the voltage within the range 230/400 V +10 %, -6 %.
At the end of this transition period, the tolerance of 230/400 V ± 10 %
should have been achieved; after this the reduction of this range will
be considered. All the above considerations apply also to the present
380/660 V value with respect to the recommended value 400/690 V.
Standard voltages between 100 V and 1000 V (IEC 60038 Edition 6.2 2002-07)