IEC Voltage Standards and Recommendations


Three-phase four-wire or three-wire systems
 Single-phase three-wire systems
Nominal voltage (V)
 Nominal voltage (V)
 50 Hz 60 Hz 60 Hz
 -
 120/208 120/240
 - 240 -
 230/400(1)
 277/480
 -
 400/690(1) 480 -
 - 347/600 -
 1000 600 -

(1) The nominal voltage of existing 220/380 V and 240/415 V systems shall evolve toward the recommended value of 230/400 V. The transition period should be as short as possible and should not exceed the year 2003. During this period, as a first step, the electricity supply authorities of countries having 220/380 V systems should bring the voltage within the range 230/400 V +6 %, -10 % and those of countries having 240/415 V systems should bring the voltage within the range 230/400 V +10 %, -6 %. At the end of this transition period, the tolerance of 230/400 V ± 10 % should have been achieved; after this the reduction of this range will be considered. All the above considerations apply also to the present 380/660 V value with respect to the recommended value 400/690 V.

Standard voltages between 100 V and 1000 V (IEC 60038 Edition 6.2 2002-07)