Coordination of Short-circuit Protection Devices
The coordination of protective equipment is the art
of associating a SCPD (short Circuit Protection Device, such as a fuse
or magnetic circuit breaker) together with a contactor and thermal
overload relay. The object of this is to interrupt an over-current (1 to
10 times the rate motor current) or short-circuit current)>10 times
the rated motor current) in sufficient time to avoid danger to either
personnel or the installation.
The prospective short-circuit
current is a characteristic of the installation at a given moment. It is
calculated by taking onto account the power source, the voltage and
line impedances (cables, connectors, transformer, etc.). The
coordination test is carried out at a conventional short-circuit current
“lq” s defined by the manufacturer of the device (for example 50 kA at
380 V for a motor starter comprising fuses + contactor + thermal
overload relay)> The standard introduces a new perspective
short-circuit current “lr” according to the AC-3 rated operational
current of the device, such that lr < lq (for example: for 63 A, lr =
3 kA). The coordination must always be checked for both lr and lq at
the same time.
The IEC 947 standard defines two types of starter, SCPD coordination:
- Type1 (previously type “a” in IEC 292-1)
Upon
a short circuit, the equipment must not present a danger to personnel
or installations. After disappearance of the short circuit, the device
cannot be operated again without repair or replacement of parts.
- Type 2 (previously type “c” in IEC 292-1)
Upon
short circuit, the equipment must not present a danger to personnel or
installations. After disappearance of the short circuit, the device
should not show deterioration or altered settings. Any welded contacts
on a contactor must be easily separable. No replacement parts are
permitted in the course of the test, except for fuses, which must all be
changed.